PROFLAME SYSTEM
TROUBLESHOOTING GUIDE
This document is intended to be to be used by the appliance manufacturer only
and is not to be distributed to field service personnel or the end user.
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - PROFLAME SYSTEM

9.957.074 00 PROFLAME SYSTEMTROUBLESHOOTING GUIDEThis document is intended to be to be used by the appliance manufacturer only and is not to be dis

Page 2

104Fan turns on?Are you usingremote transmitterGTMF or GTMFS?1.Replace transmitter with GTMF or GTMFS versionNO NOYESFan RPM changes inaccordance with

Page 3

11Replace receiver battery with new onesIs receiver beeping? 1. Replace the receiverReplace transmitter battery with new onesPushing ON/OFF button oft

Page 4 - 880/886 Proflame

12OFF command troubleshooting fl ow chartOFFcommandMain burnerturns OFF?NO1. Verifiy transmitter-receiver communication2. Remove the electrical wire co

Page 5 - GTMS Profl ame system (Fig.3)

136 Additional troubleshooting information 6.1 DFC power supply verifi cationBattery supply testSwitch off the FCM if present. Measure voltage between

Page 6

14This page is intentionally left blank

Page 7 - Troubleshooting fl ow chart

15This page is intentionally left blank

Page 9

2ScopeThis document is intended to be used in combination with the instruction manuals for each of the Profl ame system components to aide in trouble-s

Page 10

3by use of an OEM supplied conversion kit. The 880 valves can also be upgraded to 885 or 886 confi gurations by installing OEM supplied conversion/ kit

Page 11

43 Basic confi guration schematicsStandalone Profl ame system (Fig.1)OrangeGreenRedBlack880/886 ProflameBatteryHolderChassisconnection120 Vac INPUT7 Vdc

Page 12

5GTMFS Profl ame system (Fig.2)GTMS Profl ame system (Fig.3)REMOTEREMOTE120V OUTReceiver 14 Pin ConnectorSplit FlowPilotPinkBlueCPI / IPI MODEMOTORIPI/C

Page 13

64 ToolsManometerMultimeterFlat-headScrewdriverPhillips-headScrewdriverTest Wire5 TroubleshootingBefore proceeding with the procedures in the followin

Page 14

7Troubleshooting fl ow chartWas observed sparkat the Pilot Hood before theDFC board locked outYESNO1. Check the spark electrode positioning - adjustas

Page 15

821. Verify the pilot flame fully engulfs the tip of the sense electrode. If not replace the pilotassembly.2. Replace the sense electrode.3. Carefull

Page 16

93YESNOMainburner modulatesproperly?1. Replace the main burner orifice with a new orifice of correct size (partial blckagepossible). Verify that the m